II Parameters
FL-net Parameters
II - 133
【#29034(PR)】 Cyclic Data:Area2 Other Node Area PLC side Device
Cyclic data: Area2 Other node area CPU side device
Set the internal device used for reading the other node data in cyclic data area 2 (word
area).
---Setting range---
Within the number of device points set in the PC parameter's device setting.
【#29035(PR)】 Cyclic Data:Area2 Other Node Area Module side Transfer Cont.
Cyclic data: Area2 Other node area Module side transfer word count
Set the word count of the data used for reading the other node data in cyclic data area 2
(word area).
The standard setting is "8192".
(Note) An error will occur when the value buffer offset value exceeds "8192" after the
transfer size is added.
---Setting range---
1 to 8192
【#29036(PR)】 Cyclic Data:Area2 Other Node Area Module side Buffer off.
Cyclic data: Area2 Other node area Module side buffer offset
Set the head offset of the buffer used for reading the other node data in cyclic data area 2
(word area).
The standard setting is "0".
(Note) An error will occur when the value buffer offset value exceeds "8192" after the
transfer size is added.
---Setting range---
0 to 8192
【#29037(PR)】 Cyclic Data:Area2 Other Node Area PLC side Device
Cyclic data: Area2 Other node area CPU side device
Set the internal device used for reading the other node data in cyclic data area 2 (word
area).
---Setting range---
Within the number of device points set in the PC parameter's device setting.